Frequency converter operation

  • Converter type: Pulse-width modulation
  • Min./max. frequency during continuous duty:
    • Asynchronous motors: 30 Hz up to rated frequency (50 Hz or 60 Hz)
    • Permanent magnet motors: 30 Hz up to the stated maximum frequency as per rating plate
    • NOTICE! The maximum frequency may be below 50 Hz!
  • Min. switching frequency: 4 kHz
  • Max. overvoltage at the terminal board: 1350 V
  • Output current at the frequency converter: max. 1.5 times rated current
  • Max. overload time: 60 s
  • Torque applications: quadratic pump curve or automatic energy optimisation procedure (e.g. VVC+)
  • Required speed/torque curves are available on request!
  • Observe additional measures with regard to EMC regulations (choice of frequency converter, filters, etc.).
  • Do not exceed the rated current or rated speed of the motor.
  • It must be possible to connect the motor’s own temperature monitoring (bimetallic strip or PTC sensor).
  • If the temperature class is marked as T4/T3, temperature class T3 applies.